SEW MDP-50K Multi-Purpose Digital H. V. Phasing Meter
https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEhXK5atP4P1-qg5W7iZ83qW1L8yRNCS-h6X8VrFIc8LscDXN9bsIp0MgFmjild1EQtqpPCPt0M41cRGaUQUsT3sxt-UiEJLL8S3beVsextEcWi2mPujLXpGKNTxX8M9T3PlEYajLNrmO8c/s72-c/SEW+MDP-50K.jpg
Features :● AC 50kV and DC 50kV measurement with direct reading.
● 4000-count LCD.
● Input impedance : 400 Mohm
● Auto-ranging :
AC : 4.000kV / 40.00kV / 50.0kV
DC : 4.000kV / 40.00kV / 50.0kV
● MDP-50K must be connected with an approved hot stick,
such as HS-175, HS-120.
● Check phases are "in-phase" or "out of phase".
● Polarity indication : Positive / Negative
● Backlight function.
● Auto power off.
● Power source : 1.5V(AA) alkaline battery × 2.
● Low battery indication(Multi-level).
● Protection class : IP66
Spesification :
AC Voltage
Ranges
|
Resolution
| |
4.000 kV
|
0.001 kV
| |
40.00 kV
|
0.01 kV
| |
50.0 kV
|
0.1 kV
| |
| Accuracy | ||
0 ~ 4 kV
|
±(2.5%rdg+0.1kV)
| |
4 kV ~ 50 kV
|
±(2.5%rdg+2dgt)
| |
| DC Voltage | ||
Ranges
|
Resolution
| |
4.000 kV
|
0.001 kV
| |
40.00 kV
|
0.01 kV
| |
50.0 kV
|
0.1 kV
| |
| Accuracy | ||
0~20 kV
|
±(2.0%rdg+0.08kV)
| |
20 kV ~ 50 kV
|
±(3.0%rdg+0.1kV)
| |
| General | ||
| Low battery indication | V (Multi-level) | |
| Operating temperature & humidity |
0°C~40°C, 80% Max. | |
| Storage temperature & humidity |
-10°C~50°C, 80% Max. | |
| Dimensions | Master stick : 490(L) × 101(W) × 118(D)mm Slave stick : 490(L) × 35(W) × 35(D)mm | |
| Weight (battery included) |
Approx. 1.35kg | |
| Power source | 1.5V (AA) Alkaline battery × 2 | |