Fluke 1AC II A1 VoltAlertTM Electrical Tester 5PK
https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEie8XxpMlfwUu2sz_Q7WLkJjztjTNSy92qocpKmdrpzAP_xxoGjlxpukOj2SLLzBKqRt8I5DN1XsDyevh_7IhUvbjmbFpnIfEC4X9P5wnCHtb2320q-rPei1AcrTeYJkjATrzgtpOtS8kQ/s72-c/Fluke-1ACIIA1.jpg
Feature :
Voltbeat™
technology and continuous self-test – so you always know it's working
Upon
detection, tip glows and beeper sounds
CAT
IV 1000 V for added protection
Expanded
range: 90 V AC to 1000 V AC
20
V to 90 V AC control circuit model also available
Batteries
included
On/Off
Button
Audible/Silent
5
pack
Specifications
| Operating principles | Senses the steady state electrostatic field produced by AC voltage through insulation without requiring contact to the bare conductor. A red glow at the tip and a beeping noise (if not switched OFF) indicates the presence of voltage. |
| Voltage sensing ranges | Nominally, 90 V AC to 1000 V AC |
| Detector tip style | Flat-tip |
| Light source | One high intensity red LED |
| Agency approvals | c CSA us, CE, C-Tick |
| Safety rating | 1000 V, CAT IV |
| Safety compliance | Meets IEC 61010-1:2001, UL 61010-1 (2nd ed.), CAN/CSA-C22.2 No. 61010-1-04, and ISA-82.02.01 Pollution Degree 2 |
| EMC compliance | Meets IEC 61326-1:2006 |
| IP rating | IP 40 |
| Operating temperature | -10°C to 50°C (-14°F to 122°F) |
| Operating humidity ranges | 0% to 95% (0°C to 30°C) |
| 0% to 75% (30°C to 40°C) | |
| 0% to 45% (40 to 55°C) | |
| Operating altitude | 3000 m |
| Cleaning | Clean with damp cloth |
| Batteries | 2 AAA alkaline batteries included |
| Battery life | Typical battery life of greater than 1 year |